ANSI/TIA-568-C testing SC to ST (Duplex Multimode) DTX-EFM2
This article is for the Encircled Flux compliant DTX-EFM2 modules, testing SC to ST duplex fiber links.
The Encircled Flux requirement can be found in ANSI/TIA-526-14-C April 2015.
You can learn more about Encircled Flux (EF) at http://www.brighttalk.com/webcast/727/62347, hosted by FOTC, TIA's Fiber Optic Consortium.
Any deviation from the test method below cannot be tolerated if you wish to remain Encircled Flux compliant.
Items required in addition to a DTX CableAnalyzer:
Inspection is critical. You can use anything from a simple Fiber Viewer to a Video Scope such as the FiberInspector Mini shown above.
If you have no inspection equipment, you cannot proceed.
Let's define what is acceptable and not acceptable.
|
The Test Reference Cords (TRCs) are critical to a successful measurement. To maintain Encircled Flux compliance, you MUST use one of the following two kits:
- MRC-50EFC-SCSCKIT: Duplex MM 50 µm TRC kit for SC links (Two SC to SC EF-TRC cords and two SC to SC TRC cords)
- MRC-50EFC-SCSTKIT: Duplex MM 50 µm TRC kit for ST links (Two SC to ST EF-TRC cords and two ST to ST TRC cords)
-
You will also need two 50 µm ST to LC TRCs, which Fluke Networks does not currently offer.
o bien - MRC-625EFC-SCSCKIT: Duplex MM 62,5 µm TRC kit for SC links (Two SC to SC EF-TRC cords and two SC to SC TRC cords)
- MRC-625EFC-SCSTKIT: Duplex MM 62,5 µm TRC kit for ST links (Two SC to ST EF-TRC cords and two ST to ST TRC cords)
- You will also need two 62,5 µm ST to LC TRCs, which Fluke Networks does not currently offer.
In this example, we're going to test a 100 m (328 ft) duplex 50/125 µm multimode fiber link with SC connectors at one end and ST connectors at the other end to ANSI/TIA-568-C whilst maintaining Encircled Flux compliance to ANSI/TIA-526-14-B Oct 2010.
Setting up the DTX CableAnalyzer
-
With the DTX-EFM2 fiber modules inserted into the DTX CableAnalyzer, power up the main and remote units.
Sources will need at least five minutes to stabilize, longer in colder or hotter environments.
-
Replace the SC Adapter on the main unit with the optional ST Adapter
-
Rotate the dial on the DTX CableAnalyzer to SETUP.
-
Select Fiber Loss and press ENTER.
-
Change the Test Limit to TIA-568-C Multimode.
-
Change the Fiber Type to the cable you are testing.
This setting changes the Refractive Index (n) value. The DTX uses n to calculate the length of the fiber. You can manually enter the n values in Tab 3 of the Setup. If you cannot find your cable in the DTX Cable Library, look to the cable vendor's website for their datasheet. Since the TIA-568-C Multimode limit is calculated based on length, it is important to get this value right.
-
The Number of Adapters is going to be 2.
This is always the number of adapters per fiber strand added after the reference has been set.
-
Set the Connector Type to SC.
This will not affect the outcome of the result. It only affects the help screens.
-
Set the Test Method to 1 Jumper.
-
Inspect the TRCs. If needed, clean them and inspect again. You will not know if they are clean or not until you have visually inspected them.
-
Connect the Output port on the main unit to the Input port on the remote unit as shown below.
EF-TRCs must be used. Failure to do so will result in non Encircled Flux compliance.
-
Connect the Output port on the remote unit to the Input port on the main unit as shown below.
EF-TRCs must be used. Failure to do so will result in non Encircled Flux compliance.
-
Rotate the dial to SPECIAL FUNCTIONS.
-
With Set Reference selected, press ENTER then TEST.
-
You will then be presented with the results of the Reference.
For 50/125 µm it should be better than -24,50 dBm where -23,50 dBm is better than -24,50 dBm.
For 62,5/125 µm it should be better than -20,00 dBm where -19,50 dBm is better than -20,00 dBm.
These values reflect the cleanliness of the Ports and TRCs. The fact that your reference values are better than the minimum stated above does not mean they are good/clean.
-
Press F2 OK.
-
You can enter the length of your TRCs here. It does not affect the outcome of the test, but will be displayed on the test report.
-
Press F2 OK when done.
-
Rotate the dial to AUTOTEST and press TEST.
-
We're looking to make sure the sources have stabilized, so with Loss (Remote > Main) highlighted, press ENTER.
If you see the loss deviate from 0,00 dB by more than 0,02 dB, your sources have not stabilized. This is an important step to avoid negative loss readings.
Press EXIT and then highlight Loss (Main Remote) followed by ENTER.
Again, if you see the loss deviate from 0,00 dB by more than 0,02 dB, your sources have not stabilized. This is an important step to avoid negative loss readings.
-
Remove the ST and SC connectors from the Input Ports. Never disconnect from the Output Ports. Doing so invalidates the reference you just set.
-
Insert the ST to SC TRC' into the Input Port on the main unit.
-
Insert the SC to ST TRC into the Input Port on the remote unit.
-
You are now ready to test the fiber link. There is no easy way to verify the TRCs so inspection is going to be critical. This method is far more precise thany any other method that may result in negative loss readings. You could build yourself a reference link to verify your TRCs.
-
Connect the TRCs to the link you're testing.
- Press TEST.
The DTX CableAnalyzer will calculate the test limit (optical loss budget) for you.
Changing the number of adapters/splices will of course increase the test limit. Be sure the Number of Adapters is set correctly.
How often should I Set Reference?
The quick answer is; every time you begin to test a series of fiber links. It is critical to continually inspect the TRCs.