Fiber Optic Cable Testing Methods

Fiber optic networks are the backbone of modern telecommunications, providing high-speed data transmission over long distances with minimal loss. The performance and reliability of these networks depend on the quality of the fiber optic cables and the precision of their installation. This is why fiber optic cable testing is critical.

Fiber optic testing ensures the performance and reliability of fiber optic networks. These test procedures assess the physical and functional qualities of fiber optic cables, connectors, and the network as a whole. Key tests include:

  • Measuring signal loss
  • Verifying the strength and quality of the fiber
  • Ensuring compliance with industry standards

Effective fiber testing utilizes advanced tools such as Optical Loss Test Sets (OLTS), Optical Time-Domain Reflectometers (OTDR), and Visual Fault Locators (VFL) to diagnose and correct issues, ensuring optimal network performance. Such a comprehensive approach to fiber optic cable testing safeguards the integrity of data transmission.

Fluke Networks provides comprehensive solutions for fiber optics testing, ensuring your network performs at its optimal level.

What Is Fiber Testing?

Fiber testing evaluates fiber optic cables' performance characteristics and integrity. It verifies the functionality and efficiency of newly installed and existing fiber optic networks. Careful and comprehensive fiber optics testing helps technicians detect issues such as signal loss, interference, and physical damage to the cables, any of which can severely impact network performance.

What Are the Methods of Fiber Testing?

There are several methods of fiber optic cable testing, each serving a specific purpose in assessing the cable's performance and reliability:

  • Optical Loss Test Sets (OLTS): This method measures the total light loss in a fiber optic link, simulating the network conditions.
  • Optical Time-Domain Reflectometer (OTDR): OTDR testing involves sending pulses of light down the fiber to detect faults, bends, and splice losses by analyzing the light scattered or reflected.
  • Visual Fault Locator (VFL): VFLs use a visible light laser to identify breaks and tight bends in the fiber optic cable.
  • Fiber Inspection Probes: These devices magnify the end face of a fiber connector, allowing technicians to find dirt, debris, or damage that could impede performance.

What Are the Standards for Fiber Optic Cable Testing?

Industry standards in fiber optic cable testing are crucial for ensuring a fiber optic network’s consistency, reliability, and interoperability. The key standards organizations include:

  • TIA/EIA: Sets standards for fiber optic cable system design, installation, and testing in North America.
  • IEC: Sets international standards covering various fiber optics testing procedures and parameters.
  • ISO: Provides quality management and assurance standards, including those relevant to fiber optic testing.

What Are the Different Types of Fiber Optic Cable Testing?

Fiber optic cable testing can be categorized based on the type of test being conducted:

  • End-to-End Testing: Verifies light transmission capability and signal integrity over the entire length of the cable.
  • Pruebas con OTDR: Identifies the location and severity of faults within the cable or its connectors.
  • Insertion Loss Testing: Measures the loss of signal power resulting from the insertion of a device in a transmission path.
  • Return Loss and Reflectance Testing: Assesses the amount of light reflected back toward the source, which can cause signal degradation.

Configuraciones de cableado

Las configuraciones de cableado pueden tener estas formas conocidas:

  • Adaptadores o tomas en ambos extremos del cableado
  • Conectores en ambos extremos del cableado
  • Plug on one end, adapter on the other end of the cabling
  • Plugs on both ends of the cabling using equipment cords

Existen cinco métodos únicos de comprobación que pueden usarse para comprobar las cuatro configuraciones de cableado:

  • Método de un cable
  • Método de dos cables
  • Método de tres cables
  • Método de tres cables mejorado
  • Método de cable de equipo o canal

The one-cord method is used for permanent link testing and calls for the launch cord to be attached directly to the power meter for the reference and assumes the power meter has an interchangeable adapter. Se utiliza cuando el cableado bajo prueba tiene adaptadores o tomas en ambos extremos del cableado. El método de un cable siempre es el método preferido siempre que sea posible ya que cuenta con la menor incertidumbre de medición.

The two-cord method is used for permanent link testing and can be used for two cabling configurations. Primero, cuando hay conectores en ambos extremos del cableado. Y segundo, cuando hay un conector en el extremo de un cable y un adaptador en el otro extremo. El método de dos cables esencialmente mide el cableado pero sola la conexión de un extremo.

El método de tres cables excluye la atenuación de ambas conexiones al cableado bajo prueba. Se puede usar cuando los latiguillos se empalmen en ambos extremos del cable y directamente conectados a equipos de transmisión. Este método puede también utilizarse para la comprobación de canales cuando los mejores métodos no son prácticos.

El método mejorado de tres cables incluye la atenuación de ambas conexiones al cableado bajo prueba y puede utilizarse para la medición de enlaces. This method can be used for permanent link measurements when the connectors on each end of the cabling are different from each other, making the one-cord method difficult.

El método de comprobación de cable/canal de equipo se utiliza cuando los cables del equipo están instalados en ambos extremos del cableado y están esperando conexión a equipos de transmisión. Este método se utiliza para las mediciones de atenuación de canal. Este método tiene menor incertidumbre que el método de tres cables pero puede ser más difícil de utilizar.

La tabla 1 resume los estándares de medición de atenuación conocida para el cableado de fibra óptica instalada, sus métodos de comprobación y más importante, cuándo se deben utilizar. Un estudio cuidadoso de la tabla revelará superposición entre los estándares. El método único de comprobación que se especifica en un solo estándar es el método de tres cables mejorado.

Métodos de comprobación definidos por estándares
Estándar Métodos de comprobación Cuando se utilizan Comentario
TIA-526-14-C, adaption of IEC 61280-4-1, edition 2 De un cable Required test method for links when adapters are attached to plugs or sockets at both ends of the cabling.  
De dos cables Método de comprobación requerido para enlaces con conectores mixtos en ambos extremos del cableado, donde uno de los extremos se termina con un adaptador y el otro extremo se termina con un conector.  
De tres cables Método de comprobación requerido para enlaces con conectores en ambos extremos del cableado.  
IEC 61280-4-1, edition 3 in revision De un cable Método de comprobación requerido para enlace cuando los adaptadores están conectados a enchufes o tomas a ambos extremos del cableado. Assumes the connector on the power meter is compatible with the cabling under test into which the launch cable is connected (power meter has interchangeable adapter).
De dos cables Required test method for links that have plugs on both ends of the cabling; Required test method for links with mixed connectors on both ends of the cabling, where one end is terminated with an adapter and the other end is terminated with a plug  
De tres cables Comprobación de enlaces como el método alternativo para los métodos de uno, dos y tres cables de equipo.  
Cable de equipo Required test method for links with plugs on both ends of the cabling utilizing equipment cords Principalmente una variante del método de 1 cable.
TIA-526-7, adopción de la norma IEC 61280-4-2, edición2 De un cable Método de comprobación requerido para enlace cuando los adaptadores están conectados a enchufes o tomas a ambos extremos del cableado. Straight adoption, no adaptation so contents from IEC 61280-4-2 are the same.
De dos cables Método de comprobación requerido para enlaces con conectores mixtos en ambos extremos del cableado, donde uno de los extremos se termina con un adaptador y el otro extremo se termina con un conector.
De tres cables Método de comprobación requerido para enlaces con conectores en ambos extremos del cableado.
TIA-568.3-D Como se indica en TIA 526-7 and TIA 526-14. La comprobación de canales debe utilizar el método de tres cables según lo definido por estándares del IEC, no estándar el de comprobación de ISO/IEC. One-cord method is preferred for both multimode and single-mode links.
ISO/IEC 14763-3, edición 2 De un cable Atenuación de enlace cuando el cableado bajo prueba tiene la misma interfaz que el medidor de potencia; mide el enlace permanente. Amendment in process
Método de tres cables Atenuación de enlace cuando el cableado bajo prueba tiene diferentes conectores en cada extremo del cableado; mide el enlace permanente.
Canal Atenuación de canal utilizando los cables de equipo (cliente) no incluye las conexiones a equipos (transceptores); mide el canal.
ARINC 805 Un cable para multimodo y monomodo Método de prueba requerido Based on TIA-526-7 (SM) and TIA-526-14 (MM)

 

Permanent link test includes the attenuation of both connections on each end of the cabling under test. Channel test does not include that connection attenuation between the equipment cord and transceiver.

MÉTODO DE UN CABLE

a. Establezca una referencia entre la fuente de luz y el medidor de potencia usando el cable de lanzamiento (ver la figura 3).

Figura 3. Fije la referencia.

 

a. Coloque un cable de recepción en el medidor de potencia.

b. Conecte el cable de lanzamiento y de recepción al cableado bajo prueba (ver la figura 4).

c. Make the measurement and compare to the reference measurement

Figura 4. Mida atenuación del cableado, conexión A y conexión B

MÉTODO DE DOS CABLES

a. Establezca una referencia entre la fuente de luz y el medidor de potencia usando el cable de lanzamiento y recepción (ver figura 5).

Figura 5. Fije la referencia.

 

b. Realice la medición y compare a la medición de referencia (ver figura Figure 6a y Figure 6b).

c. Para el caso 2, un cable de adaptador se convierte en parte del cable de lanzamiento (ver figura 6b)

Figura 6a. Medir atenuación para el caso 1 (adaptador de conector y conector en los extremos del cableado)

 

 

Figura 6b. Medir la atenuación para el caso 2 (ambos extremos del cableado se conectan)

MÉTODO DE TRES CABLES

a. Establezca una referencia entre la fuente de luz y el medidor de potencia usando el cable de lanzamiento, reemplazo y recepción (ver figura 7).

Figura 7. Fije la referencia.

 

a. Retire el cable de sustitución y reemplácelo con el cableado bajo prueba.

b. Realice la medición y compare a la medición de referencia (ver figura 8).

Figura 8. Medir la atenuación

MÉTODO DE TRES CABLES MEJORADO

a. Establezca una referencia entre la fuente de luz y el medidor de potencia usando el cable de lanzamiento (ver la figura 9).

Figura 9. Establecer la referencia usando el método de un cable

 

a. Agregue un cable de recepción para el medidor de potencia y un cable de sustitución entre los cables de lanzamiento y recepción y compruebe que no haya conexiones de baja pérdida como 0,4 dB para monomodo (ver figura 10).

Figura 10. Compruebe que no haya conexiones de baja pérdida

 

a. Retire el cable de sustitución y reemplácelo con el cableado bajo prueba.

b. Mida la atenuación del cableado y compare a la referencia (ver figura 11).

Figura 11. Medir la atenuación

CABLE DE EQUIPO, MÉTODO DE COMPROBACIÓN DE CANAL

a. Establezca la referencia usando el cable de lanzamiento y cable de primer equipo conectado a la fuente de luz (ver figura 12).

Figura 12. Fije la referencia.

 

a. Agregue el segundo equipo de cable al medidor de potencia.

b. Conecte los cables del equipo al cableado y mida la atenuación (ver la figura 13).

Figura 13. Medir la atenuación

Resumen

Entender la diferencia entre un enlace permanente y canal puede ser un desafío y saber qué método de comprobación aplicar es confuso sobre todo para configuraciones híbridas. Estas configuraciones híbridas existen y entender como comprobarlas es un beneficio para los instaladores. Existen varios estándares para la comprobación pero los estándares también se superponen para los métodos de comprobación. La Tabla 1 proporciona un resumen útil de los varios estándares, qué método debe utilizarse y cuál método debe aplicarse basado en la configuración de cableado. Mientras que existen otros métodos de comprobación disponibles, Fluke Networks sigue recomendando el método de un cable para todas las comprobaciones.

Learn more about fiber optic testers, tools, and troubleshooting on our Fiber Optic Testers page.